Wire Size Calculator

Enter the load current, one-way length and allowed voltage drop to estimate the minimum copper cross-section by BS7671 voltage-drop method, for home and light-commercial wiring selection.

Input Data

Current
A
Length
m
Voltage
V
Drop Pct
%

Results

2ρL I / ΔV.
1.5mm²
Selected
1.5mm²

At a glance:Select by voltage drop: allowed drop ΔV = V × pct/100; required copper cross-section A = 2·ρ·L·I / ΔV (ρ copper 0.0172 Ω·mm²/m, 2 is the outgoing+return path). Round up to a standard gauge (1, 1.5, 2.5, 4, 6, 10, 16…). This calculator only sizes by voltage drop and does NOT include current-carrying capacity (overload/heat) or protection coordination; in practice verify current rating per BS7671 as well.

Formula

ΔV = V × drop%

Cross-section = 2 × ρ × L × I / ΔV

$$\Delta V = V \cdot p$$
$$A = \frac{2 \rho L I}{\Delta V}$$

How to Use

  1. Enter the load current (A).
  2. Enter the one-way length (m).
  3. Enter the system voltage and allowed drop%.
  4. The tool outputs the minimum cross-section and suggested gauge.

Case Studies

Living-room socket circuit

20 A, 15 m, 230 V, 3%.

Min cross-section about 2.2 mm²; choose 2.5 mm².

Remote water pump

32 A, 40 m, 230 V, 5%.

Min cross-section about 4.8 mm²; choose 6 mm².

FAQ

Why is voltage drop alone not enough?

Real wire selection must meet voltage drop, current-carrying capacity (no overheat) and MCB coordination at once — take the strictest of the three.

What resistivity for copper?

Room-temperature copper is about 0.0172 Ω·mm²/m; at high temperature or continuous load you may increase it slightly for safety margin.

Related Tools

References

Content review: Calculatorism Editorial Team. Results are for reference only; please refer to the relevant authorities for the official figures.

Found a problem with the results?

If this calculator's result is wrong, or you have any question about the calculation logic, please let us know. You are viewing:Wire Size Calculator(/construction/wire-size)。